| 1 |
Type |
Addressable |
| 2 |
Model |
TI-002317-V |
| 3 |
Base Technology |
Dual flash-based processors with real-time clock, trace diagnostics, programmable
languages and character sets |
| 4 |
Display |
White backlit 240 x 64 graphical LCD |
| 5 |
LED Indicators |
22 red (1 x Fire, 1 x More Alarms, 20 x Zonal Programmable), 1 green (Power), |
| 6 |
Controls |
Alphanumeric keypad permitting navigation, Reset, Mute, Silence, Resound, Evacuate,
and 4x programmable push buttons |
| 7 |
Protocol |
Fully digital communication protocol |
| 8 |
Number of Fire Zones |
2000 (200 per individual panel) |
| 9 |
Number of Loops |
1 |
| 10 |
Devices per Loop |
240 Addressable Detectors and Devices |
| 11 |
Loop Current |
500mA |
| 12 |
On-Board Sounder Circuits |
2x1 Amp programmable |
| 13 |
On-Board Relays |
2x1Amp 30vAC/DC programmable(10mA,5vmin)-expandable to 4 TI-002370
(2-Way Relay Card) |
| 14 |
Auxiliary Supply |
1 x 24v500mA |
| 15 |
Programmable Input |
1 x monitored programmable input on-board |
| 16 |
Programmable Key Switch Inputs |
1 x volt free input (standard enc.), 8 x inputs (Only with medium enclosure
panel TI-002317-VM) |
| 17 |
Total Available Output Current |
3A maximum available for loop current + sounder outputs + auxiliary supply |
| 18 |
Mains Supply |
200 - 240v 47-63 Hz AC (+10%, -15% tolerance) 1.0AMax |
| 19 |
Charger Current |
1A temperature compensated |
| 20 |
Serial Port |
1 x on-board RS232 connection for PC, modem, IP, or portable printer |
| 21 |
USB Interface |
1 x USB B type connection for PC communication |
| 22 |
Programming |
On-board keypad or PC running Windows tools |
| 23 |
Event Log |
5000 event & diagnostic + 500 fire |
| 24 |
Networking |
Optional plug-in network card (TI-002325 - standard, or TI-002324 -fault-tolerant) |
| 25 |
Printer (optional) |
On-board (only with medium enclosure panel TI-002317-VM) |
| 26 |
Enclosure/Colour |
Steel IP30 /RAL7035 |
| 27 |
Metal work Options |
Flushing bezel, battery box, utility enclosure, termination enclosure and rack mount |
| 28 |
Approvals |
EN 54-2:1998, EN 54-4:1998 & EN54-13:2005 |