| 1 |
Type |
Addressable |
| 2 |
Model |
TI-002320-FT |
| 3 |
Base Technology |
Dual flash-based processors with real-time clock, trace diagnostics, programmable
languages and character sets |
| 4 |
Display |
White backlit 240 x 64 graphical LCD |
| 5 |
LED Indicators |
22 red (1 x Fire, 1 x More Alarms, 20 x Zonal Programmable), 1 green (Power), 13 amber
and 7 bi-colour (Fault & System) |
| 6 |
Controls |
Alpha numeric keypad permitting Navigation, Reset, Mute, Silence, Resound, Evacuate,
and 4 x Programmable Push Buttons Actual 2 |
| 7 |
Protocol |
Fully digital communication protocol |
| 8 |
Number of Fire Zones |
2000 (200 per individual panel) |
| 9 |
Number of Loops |
Dedicated 2-8 loop control panel |
| 10 |
Devices per Loop |
240 Addressable Detectors and Devices |
| 11 |
Loop Current |
500mA |
| 12 |
On-Board Sounder Circuits |
8x1 Amp programmable |
| 13 |
On-Board Relays |
4x1Amp 30vAC/DC programmable (10mA,5vmin)-expandable to 8 using
2x TI-002370 (2-Way Relay Card) |
| 14 |
Auxiliary Supply |
2 x 24v500mA |
| 15 |
Programmable Input |
2 x monitored programmable input on-board |
| 16 |
Programmable Key Switch Inputs |
16 volt free digital inputs |
| 17 |
Total Available Output Current |
2 x 5A maximum available for loop current + sounder outputs + auxiliary supply |
| 18 |
Mains Supply |
200 - 240v 47-63 Hz AC (+10%, -15% tolerance) 1.4Amax |
| 19 |
Battery Capacity |
2 x 24V4Ah internal(min),2x24V,18Ah internal(max), or 1x24V45Ah internal(max)
and1x24V 45Ah external (max) using optional battery enclosure |
| 20 |
Charger Current |
2 x 2A temperature compensated |
| 21 |
Serial Port |
2 x on-board RS232 connection for PC, modem, IP, or portable printer |
| 22 |
USB Interface |
2 x USB B type connection for PC communication |
| 23 |
Programming |
On-board keypad or PC running Windows tools |
| 24 |
Event Log |
2 x 5000 event & diagnostic + 500 fire |
| 25 |
Networking |
On-board Fault-tolerant network card (TI-002324). |
| 26 |
Printer (optional) |
On-board |
| 27 |
Enclosure/Colour |
Steel IP30 /RAL7035 |
| 28 |
Cable Entry (20mm knockouts) |
30 x top, 6 x rear, 3 x bottom plus 2 x double knockout rear |
| 29 |
Approvals |
EN 54-2:1998, EN 54-4:1998 & EN54-13:2005 |